SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Operation · Fault codes · Troubleshooting
Zobrazit stránku 0
1 2 3 4 5 6 ... 31 32

Shrnutí obsahu

Strany 1 - SYSTEM MONITOR

Edition GB – W12SYSTEM MONITOR FOR REMKO SUPERTEC INVERTEROperation · Fault codes · Troubleshooting

Strany 2

Setting on SW2 System component Measuring range and description UnitCondenser operating time0 – 9999 0 – 9999If the number is above 99, the display sw

Strany 3 - Contents

Setting on SW2 System component Measuring range and description UnitNew fault message on the outdoor unit (1)The last message in the fault list is del

Strany 4

Setting on SW2 System component Measuring range and description UnitOperating current of the con-denser before fault0 – 20 0 – 20 AON1 2 3 4 5 6List

Strany 5 - Description

Setting on SW2 System component Measuring range and description UnitUnit output Display takes the form of a capacity code Unit output: capacity codeCM

Strany 6

Setting on SW2 System component Measuring range and description UnitHeat exchanger temperature sensor on the outdoor unit (two-phase mixture) TH6-39 –

Strany 7

Setting on SW2 System component Measuring range and description UnitSubcooler temperature SC0 – 130Cooling: TH6 - TH3Heating: TH5 - TH4 0 – 130If the

Strany 8

Setting on SW2 System component Measuring range and description UnitDC bus voltageCMF 80/90/140/150CMT 100/150180 - 370180 – 370 If the voltage is ove

Strany 9

Setting on SW2 System component Measuring range and description UnitOpening width of the LEV A before fault0 – 480 0 – 480If the opening width is over

Strany 10 - REMKO SYSTEM MONITOR

Setting on SW2 System component Measuring range and description UnitOutdoor temperature TH7 before fault-39 – 88 -39 – +88If the temperature sensor me

Strany 11

Setting on SW2 System component Measuring range and description UnitSwitch-on duration untilfault0 – 999 0 – 999If the duration is over 99 min., the d

Strany 13

Fault codesWhen a fault occurs, the fault code is issued on the outdoor unit using flashing codes on two LEDs ! CAUTIONPlease note the following

Strany 14

Fault code displayDescription LED 1 (green) LED 2 (red) DisplayFlashes 3 timesFlashes onceU2Hot gas temperature sensorInternal thermostat of compresso

Strany 15

Fault code Meaning Cause Remedial measuresNo displayand no function_No supply voltage is present at terminal block TB1.The main switch connected upstr

Strany 16

Fault code Meaning Cause Remedial measuresF1Phases reversed, power supply, polarity reversed on connection and control cables to the indoor unit1. Thr

Strany 17

Fault code Meaning CauseRemedial measuresF9High and low pressure switches 63H, 63L Thermal relay 51CM If the circuits of the identified components repo

Strany 18

Fault code Meaning Cause Remedial measuresU1High pressure too high (63H was triggered)The high pressure switch 63H was triggered because the high pres

Strany 19 - 1 2 3 4 5 6

Fault code Meaning CauseRemedial measuresU2Refrigerant levelIncorrect if the hot gas overheating in cooling mode TH4–TH5 / in heating mode TH4–TH6 ris

Strany 20

Fault code Meaning CauseRemedial measuresU4Open circuit/short-circuit on the temperature sensors of the outdoor unit (TH3, TH32, TH33, TH6, TH7 and TH

Strany 21

Fault code Meaning Cause Remedial measuresU6Power modules in the inverter circuit defective.If overcurrent is detected in the inverter circuit ("

Strany 22

Fault code Meaning Cause Remedial measuresU9Overvoltage or undervoltage in the inverter and fault in the serial communication of the circuit boards.Dr

Strany 23

ContentsRead this installation manual carefully before commissioning / using the device!These instructions are an integral part of the system and mus

Strany 24

Fault code Meaning Cause Remedial measuresUEHigh pressure fault, 63H was triggeredThe high pressure protective switch detected 4.14 MPa in heating mod

Strany 25

Fault code Meaning CauseRemedial measuresULLow pressure fault (63L was triggered).If one of the two following conditions are met in heating mode for a

Strany 26

Hotline Air conditioning and heat-ing technology +49 5232 606-0 Export +49 5232 606-130REMKO GmbH & Co. KG Air conditioning and heating technology

Strany 27

Safety notesDisposing of packagingAll products are packed for trans-port in environmentally friendly materials. You can make a valuable contribution t

Strany 28

The equipment is delivered in sturdy transport packaging. Immediately check the equipment on delivery and make note of any damage or missing parts on

Strany 29

Shut down the system using the heat pump manager. Switch off the power supply of the outdoor unit. Remove the right side panel. This is achieved

Strany 30

DIP switch SW 2 during normal operation Switch off the power supply of the outdoor unit. To do so, set switches 1-6 of SW2 to their initial setting

Strany 31

If the condenser is switched off by a protective device after a faulthas occurred, the LED display al-ternates between showing the unit address of the

Strany 32 - REMKO INTERNATIONAL

Hot gas temperature TH43 – 217Number of switch on/off pro-cedures of the condenser0 – 99993 – 217If the temperature sensor measures values above 99°C,