Edition GB – W11REMKO CMF / CMTCMF 120-1P, CMF 160-1P, CMT 120-1P, CMT 160-1PInverter heat pumpsPlanning Guide and Installation Manual Instructions fo
REMKO CMF / CMTDefrost by circulation reversalAt temperatures below about +5°C, humidity freezes in the evaporator (outdoor module) and an ice layer c
CMF SeriesWe offer two different indoor-unit designs. The wall-mounted CMF Series is equipped with a circulation pump and a safety module on the water
REMKO CMF / CMTCMT SeriesIn addition, the indoor module of the CMT series is fitted with a hot-water buffer storage. An electric booster heater with a
Outdoor unit CMT 120-1PIndoor unit CMT 120-1PFanOutdoor areaRefrigerant lines 3/8" and 5/8"Mains cable Indoor unit (3x1.5mm2)Indoor area
REMKO CMF / CMTÖOutdoor unit CMT 160-1PIndoor unit CMT 160-1PFanOutdoor areaRefrigerant lines 3/8" and 5/8"Mains cable Indoor unit (3x1.5mm2
These instructions are to be observed when installing the entire system. The device should be delivered as near as possible to the site of installa
REMKO CMF / CMT The wall bracket is to be attached to the wall with the fasteners supplied and the indoor module hooked onto it. The wall must posse
The device may be attached only to a load-bearing structure or wall. Ensure that the outdoor module is installed only vertically. The installation s
REMKO CMF / CMTMinimum distances in mm for CMF/CMT 120-1P and in brackets for the CMF/CMT160-1P depending on the enclosureNext to a wall, air outlet
Condensate- and melt-water drainageSpecial attention must be directed to the topic of condensate- and melt-water drainage. In every case, steps must b
REMKO CMF / CMTHydraulic connection We recommend installing a buffer storage unit as a hydraulic switch for hydraulically isolation of the heating ci
Corrosion protectionOxygen always plays a role if metal materials in a heating system corrode. pH values and the salt content also play a major role.T
REMKO CMF / CMTElectrical connection It is necessary to lay a power-supply cable both to the outdoor module and, separately, to the indoor module.
Electrical connection - indoor moduleThe following instructions describe the electrical connection of the CMF and CMT Series indoor module. Shown her
REMKO CMF / CMTElectrical connection - outdoor module The side wall of the the unit is to be removed by means of loosening the screws in order to c
Temperature sensors External sensor The number of sensors required can vary with the type of system. In the indoor module (F11), the collector sens
REMKO CMF / CMT The outdoor- and the indoor modules are connected with two copper pipes of refrigerator quality having the dimensions “ and “ (REMKO
Monitoring for leaks Connect the manometer to at least one Schrader valve on the shut-off valves of the outdoor module. The leak test must to be un
REMKO CMF / CMTControl panel Mode switch Position I: Normal operation This switch turns on the system. The heat pump and a possible 2nd heat source
Notes for commissioning The commissioning and programming of the heat-pump manager may be carried out only by an installer authorized by REMKO. N
ContentsRead these operating instructions carefully before commissioning / using this device!These instructions are an integral part of the system an
REMKO CMF / CMTHeat pump manager Multi-Talent Plus (heat flow meters)Display levelThe displays relevant to the heat flow meters are called up with the f
Troubleshooting and customer serviceThe unit has been manufactured using state-of-the-art production methods and tested several times to ensure its co
REMKO CMF / CMTDisplay Fault description/noteHeat-pump fault (E 54)Heat pump fault The flow monitor has tripped. A flow problem has occurr
In the event that the red control lamp lights up on the indoor module, then the fault is on the outdoor module. Two LEDs are visible after removing th
REMKO CMF / CMTUnit dimensionsDimensions outdoor module CMF / CMT 120-1PDimensions outdoor module CMF / CMT 160-1P45070010501338450135034
Unit dimensionsPipe-socket arrangementOpening for installing the E-heater controllerRefrigerant pipe, 3/8"Condensate-drain socket AD=22Fill- and
REMKO CMF / CMTExternal dimensions, CMT Series indoor moduleDimensions indoor module CMTTilt height: 1,900 mm5506059105509351670Overall dimensions: ma
REMKO CMF / CMTCircuit diagramsPlatine WP-Manager (Merlin I/O circuit board)Power plant- Disable/ enableGreen indicator light Demand Outdoor unitCircu
Circuit diagram (continued)Load pump Indoor unitCircuit diagram WP02Switching valve 2. heat sourceOPENCLOSEDSpecial accessorieselectro heatingPlatine
REMKO CMF / CMTSafety notesCarefully read the operating instruction before placing the equipment in service. It provides useful tips and information
REMKO CMF / CMTCircuit diagram (continued)Circuit diagram WP03Special accessorieselectro heatingFlow monitor *) or Jumper **)Circuit board WP manager
Circuit diagram (continued)Platine WP-Manager (Merlin I/O circuit board)Circuit diagram WP04Red indicator lightOutdoor-module failureMF4 outlet for so
REMKO CMF / CMTCircuit diagram (continued)
Circuit diagram (continued)Circuit diagram WP06 Enable 2Heat source(potential-free normally open ornormally closed switch)Enable compressorEnable Cool
REMKO CMF / CMTCircuit diagram (continued) Platine WP-Manager (Merlin I/O circuit board)Circuit diagram WP07PumpHK 1OPEN3-waymixerHK 23-wayswitching v
Circuit diagram (continued)Platine WP-Manager (Merlin I/O circuit board)Circuit diagram WP08Control panel in the indoor module(Interface PAC-IF010 B-E
REMKO CMF / CMTTerminal block/legendTermi-nalConnection layout (low-voltage sensor)X3. EarthX3.1 CAN-Bus HX3.2 CAN-Bus +X3.3 CAN-Bus LX3.4 CAN-Bus -X
Diagramm Heizleistung W35_8 kW0246810121416-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20Char
REMKO CMF / CMTCharacteristic curvesDiagramm COP W45_8 kW0123456-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Characteristic curvesPerformance number CMF / CMT 120-1PDiagramm COP W55_8 kW01234-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8
Care and maintenanceRegular care and maintenance serves to ensure trouble-free operation and long service-life of the heat-pump system.Care The indoo
REMKO CMF / CMTCharacteristic curvesPerformance number CMF / CMT 160-1PDiagramm COP W35_14kW01234567-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1
Characteristic curvesPerformance number CMF / CMT 160-1PDiagramm COP W45_14kW012345-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7
REMKO CMF / CMTDiagramm COP W55_14kW01234-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20Diagra
Pump-characteristic curves, indoor module charging pumpLevelOutput in WCurrent in AI 25 0,12II 35 0,16III 45 0,20Sound pressure levelLevelOutput in
REMKO CMF / CMTOverall sound pressure levels for outdoor module CMF/CMT 120-1P 25 63 125 250 500 1000 2000 4000 8000 A L304050607080dBHz Excluded ran
Overall sound pressure levels for outdoor module CMF/CMT 160-1PExcluded rangeOutput A-bewCursor: (A)Power=67.1 dBMiddle frequency (Hz)25 31,50 40 50 6
REMKO CMF / CMTClimatic region: -10°CExisting buildings with hot-water heating (share 18%)TypeCOPAnnual performance number with inlet/outlet tem-perat
Climatic region: -10°CExisting buildings with hot-water heating (share 18%)TypeCOPAnnual performance number with inlet/outlet tem-perature differentia
REMKO CMF / CMTSeries CMF 120-1P CMT 120-1P CMF 160-1P CMT 160-1PFunction Heating or CoolingInverter technologyREMKO SuperTecSystem Split-Air/WaterHe
Device display for outdoor module CMF 120-1P, CMT 120-1PSpare parts listNo. Designation CMF 120-1P CMT 120-1PEDP -number EDP -number1 Compressor 11200
REMKO CMF / CMTEconomical and environmentally-conscious heatingThe burning of fossil-based energy sources in order to generate power creates severe co
REMKO CMF / CMTDevice display for outdoor module CMF 160-1P, CMT 160-1PSpare parts listNo. Designation CMF 160-1P CMT 160-1PEDP -number EDP -number1 C
Device display for indoor module CMF 120-1P, CMF 160-1PWe reserve the right to modify the dimensions and constructional design as part of the ongoing
REMKO CMF / CMTSpare parts listNo. Designation CMF 120-1P CMF 160-1P1 Housing 1120009 11200092 Front panel 1120006 11200063 Door with hinge 1120005 11
Device display for indoor module CMT 120-1P, CMT 160-1P19We reserve the right to modify the dimensions and constructional design as part of the ongoin
REMKO CMF / CMTSpare parts listNo. Designation CMT 120-1P CMT 160-1P1 Housing2 Front panel, upper 1120061 11200613 Front panel, centre 1120062 1120062
EC – Declaration of Conformity We do hereby declare that the devices named below, produced and sold by us, satisfy the relevant basic requirements of
REMKO CMF / CMTGeneral termsDefrostAt outdoor temperatures below 5°C it is possible that ice may form on the evaporators of air/water heat pumps. The
Coefficient of performance The current ratio of thermal output produced by the heat pump to the consumed electrical power is referred to as the coeffi
ConsultingThanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputa
Evaporation LiquefyingCondensingDecompressionFunctional diagram heating inverter heat pumpHeating pump outdoor unitOutdoor areaHeat pump indoor unitIn
REMKO CMF / CMTLayoutBuilding type Specific heating output in W/m2Passive energy house 10Low-energy house built in 2002 40according to energy conserva
Characteristics of REMKO inverter heat pumpsOutdoor air as a heat sourceAn air/water heat pump absorbs energy from the outdoor air as its heat source