▲/▼ Buttons
The button is used to reduce the target temperature, the button
increases it. In automatic mode the temperature can be increased
or decreased by 1°C. Temperature adjustment is not possible in
dehumidifying mode.
Cooling mode
The display extinguishes
after 1 min.
Automatic mode
MODE Button
Press the MODE button to switch between the operating modes. A total
of 4 modes are available:
1. Automatic Cooling or heating mode (not supported)
2. Cooling Mainly used in summer
3. Dehumidify Used in summer or winter
4. Heating mode not supported</F>
MODEMODEMODE
Automatic Cooling Dehumidify Heating (not supported)
In automatic mode, the controller automatically selects heating or cooling
mode after it is switched on. The control range is 22 °C to 26 °C. This
can be raised or lowered using the ▲/▼ buttons.
AUTOMATIC Mode
AUTOMATIC
MODE
In cooling mode the room air is cooled to the preset target temperature.
The desired room temperature is set in 1 °C steps using the ▲/▼ buttons.
If the room temperature reaches 0.5 °C above the set target temperature,
the indoor unit starts to cool the room air. If the actual temperature falls
approx. 1 °C below the set room temperature, the controller switches the
cooling off. In order to protect the compressor, the controller will only
switch the cooling back on after a holding period of 3 minutes.
COOLING Mode
COOLING
MODE
MODE
REMKO RM
10