1) Capacities based on ISO R 859A; room temperature of TK 27°C/FK 19°C - outside temperature 35°C
2) For connection lines of 5 m or longer
3) Noise measurement DIN 45635 - 01 - KL3
Technical Data
Model RKV 13 T RKV 24 T
Cooling capacity
1)
W See corresponding outdoor part
Refrigerant R 407C
Operating range °C +15 °C to + 30 °C in 0.5 °C - steps
Connection pressure line RKS inch (mm) 3/8 (9.52)
Connection intake line RKS Inch (mm) 1/2 (12.7) 5/8 (15.9)
Connection pressure line RKM Inch (mm) 1/4 (6.35)
Connection intake line RKM Inch (mm) 1/2 (12.7)
Additional amount to add
2)
g/m 18 / 15
Dehumidification capacity l/h 1.0 2.0
Power supply V / Hz 230/1~ 50 Hz supplied via outdoor part
Power consumption W 65 80
Current consumption A 0.3 0.4
Fan capacity W 50 65
Fans speeds 3 plus automatic
max. amount of air m³/h 500 / 570 / 680 820 / 950 / 1020
Dimensions height / width / depth mm 550 / 1120 / 215 550 / 1120 / 215
Weight unit kg 22 23
VPE kg 24 25
Sound pressure level
3)
dB(A) 40 / 43 / 51 42 / 45 / 52
Infrared remote control Series
Colour White
Ref. no. 1613503 1613504
Condensation pump (accessory) Ref. no. 1613167
1120
215
550
Measurements in mm
Dimensions