Issue GB – T11
REMKO MD
MD 261, MD 351
Inverter wall - room air conditioner in split design
Operation · Technology · Spare parts
Zobrazit stránku 0
1 2 3 4 5 6 ... 31 32

Shrnutí obsahu

Strany 1 - REMKO MD

Issue GB – T11REMKO MDMD 261, MD 351Inverter wall - room air conditioner in split designOperation · Technology · Spare parts

Strany 2

HEATING- MODEHeating mode operational sequence> 6 Min.> 3 Min.> 6 Min.30 sec. 30 sec.Nominal temperature +5 °CNominal temperature +2 °CFan op

Strany 3 - Contents

The fan speed can be adjusted with this button. A selection can be made between low, medium, high and automatic fan speed.FAN ButtonFANIn ventilation

Strany 4

The activation and switch-off time can be programmed with this button. The timer is activated/deactivated by means of pressing the timer on and the ti

Strany 5 - Transport and

ShutdownTemporary shutdown1. Allow the indoor unit to run for 2 to 3 hours in air circulation mode or in cooling mode at the maximum temperature sett

Strany 6

Cleaning the condensation pump (optional equipment)An optional integrated or separate condensation pump may included on the indoor unit, which pumps o

Strany 7 - Buttons on the remote control

Troubleshooting and customer serviceThe equipment and components are manufactured using state-of-the-art production methods and tested several times t

Strany 8

Problem display by blinker codeDisplay Cause Required actionE1Communication error between outdoor component and indoor unitContact specialist firmE3 Li

Strany 9 - DEHUMIDIFICATION MODE

Selection of the installation locationIndoor unitThe indoor unit is designed for horizontal wall installation above doors. However, it can also be use

Strany 10

2001201500120120Installation inside buildings Ensure there is adequate heat dissipation when placing the outdoor component in cellars, attics, adjoin

Strany 11 - SLEEP/TURBO Button

Mounting points for wall bracket MD 261 ITMD 351 ITAll dimensions in mm750250656545815270656545Connection variations1 Outlet on the wall, right2 Ou

Strany 13 - Care and maintenance

The units are factory filled with dry nitrogen to check for leaks. The pressurised nitrogen is released when loosening the union nuts. CAUTIONCon

Strany 14

Supplementary information for Installation For the combination of the outdoor component with some indoor units, the connection of the refrigerant pip

Strany 15 - Malfunction

Condensation connection - outdoor unitOpening for condensation connectionCondensation pan of outdoor componentCondensation connectionAll electrical in

Strany 16

Check all plugged and clamped terminals to verify they are seated correctly and making a permanent contact. Re-tighten as required. CAUTION 12

Strany 17

TransformerElectrical circuit diagramMD 261-351 ITMD 261-351 ATMains cable 230V / 1~ /50 Hzto outdoor componentAir circulation sensorColour code A =

Strany 18

Add refrigerantThe equipment contains a basic quantity of refrigerant. Beyond these conditions, for refrigerant pipe lengths of more than 5 meters per

Strany 19 - Hooking in

Final tasks Re-fit all the dismantled parts. Familiarize the operator with the system. Functional test for cooling and heating modes1. Remove the cap

Strany 20

Unit dimensions Dimensional and design changes to advance technical progress are reserved.MD 261 IT / MD 351 IT280815215MD 261 AT / MD 351 AT760590270

Strany 21 - Tightness check

Exploded view MD 261-351 IT193781221011456We reserve the right to modify the dimensions and constructional design as part of the ongoing technical dev

Strany 22

Exploded view MD 261-351 ATSpare parts listNo. Designation MD 261 AT MD 351 AT1 Front panel1109761 11097782 Fan blade, liquefier1109762 11097793 Fan

Strany 23 - Indoor unit

ContentsThese operating instructions are to be read carefully prior to commissioning / operation of the device!These instructions are part of the uni

Strany 24

Technical dataSeries MD 261 MD 351Operating modeInverter-wall room air conditioner combination for cooling and heatingNominal cooling output 1)kW 2.68

Strany 26

Subject to technical modifications, no responsibility taken for the correctness of information!ConsultancyIntensive training means our consultants are

Strany 27 - Unit dimensions

Safety notesDisposal of packagingAll products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing

Strany 28

The equipment is shipped in sturdy transport packaging. Immediately check the equipment on delivery and make a note of any damage or missing parts on

Strany 29 - Spare parts list

OperationInfrared remote controlThe infrared remote control sends the programmed settings over a distance of up to 6 m to the receiver of the indoor u

Strany 30

"FAN" button Press this button to set the required fan speed. 4 settings are available: automatic, high, medium and low fan speed. &quo

Strany 31

A symbol is shown on the display to indicate that the settings are being transferred.By pressing the ON / OFF button, you can activate or deactivate y

Strany 32 - REMKO ACROSS EUROPE

> 6 Min.> 3 Min.> 6 Min.30 sec. 30 sec.Nominal temperatureNominal temperature -2°CFan operation ITFan operation ATCompressor operation ATActu